41
Foutnummer
126-0117
126-0118
126-0119
2160
Beschrijving
Error message
PLC-uitgang voor uitschakelen verkeerd geconfigureerd
Cause of error
The PLC output for switching off the machine after the
control has been shutdown was incorrectly configured.
The settings in the configuration datum CfgShutdown are
not applicable for an integrated PL (e.g. with UEC, UMC) nor
for a PL connected over HSCI (e.g. PLB 62xx).
Settings for output on internal PL:
- powerOffDevice: Unassigned
- powerOffSlot: Unassigned
- powerOffPort: Number of the output on internal PL (value
range: 0 to 30)
Settings for output on a PL connected over HSCI:
- powerOffDevice: Bus address of the PL
- powerOffSlot: Slot number of the module (0 for system
module and UEC11x)
- powerOffPort: Number of the output to be switched
Error correction
- Check the configuration data (machine parameter number
101600)
- Inform your service agency
Error message
PLC-uitgang voor uitschakelen verkeerd geconfigureerd
Cause of error
Automatic machine switch-off after control shutdown has
been selected. However, no PlC output was defined for it in
the configuration file nor in the IOC file.
Error correction
- Define a PLC output for switch-off in the IOC file or in the
configuration file
- Inform your service agency
Error message
Keyname %1 voor OEM-script te lang
Cause of error
- De gebruikte keynaam voor het Python-script dat bij het
opstarten moet worden gestart, is te lang. Maximaal 10
tekens toegestaan.
Error correction
- Configuratiedatum wijzigen
NC-foutmeldingen | Lijst met NC-foutmeldingen
HEIDENHAIN | TNC7 | TNCguide | 01/2022