Transducer Block Parameters (Slot 5)
In de onderstaande tabel worden de Transducer Block parameters weergegeven met de Transmitter
specifieke configuratie parameters. Index parameters 25, 27, 43, 44, 45, 53 en 54 kunnen alleen
geconfigureerd worden indien de transmitter is ingesteld op Out of Service (OOS). De transmitter
kan ingesteld worden op Out of Service met index number 21. Nadat het Tranducer Block
geconfigureerd is, dient de transmitter met index number 21 weer op AUTO gezet te worden.
Index Name
16
BLOCK_OBJECT
Reserved
Block_Object
Parent_Class
Class
Dev_Rev
Dev_Rev_Comp
DD_Revision
Profile
Profile_Revision
Execution_Time
Number_of_Parameters
Address_of_View_1
Number_of_Views
17
ST_REV
18
TAG_DESC
19
STRATEGY
20
ALERT_KEY
21
TARGET_MODE
22
MODE_BLK
Actual_mode
Permitted_mode
Normal_mode
23
ALARM_SUM
Current
Unacknowledged
Unreported
Disabled
24
PRIMARY_VALUE
Value
Status
25
PV_UNIT
26
SECONDARY_VALUE
Value
Status
27
SV_UNIT
28
TERTIARY_VALUE
Value
Status
29
TV_UNIT
30
QUATERNARY_VALUE
Value
Status
NL-4000-PROFIBUS-PA-04-2023-
02
Type
Description
Record
Block object
Unsigned8
0
Unsigned8
0x03, transducer block
Unsigned8
244, manufacture specific
Unsigned8
250, not used
Unsigned16
1
Unsigned16
1
Unsigned16
0
MSB: 0x40 -> Number of the PROFIBUS PA
OctetString(2)
profiles within PI Profile Class 64
LSB: 0x02 -> Class B
Unsigned16
0x302: PA Profile Revision 3.02
Unsigned8
0
Unsigned16
52, number of parameters
Unsigned16
0x05F8, View_1 has an index 248
Unsigned8
1, one View_1
ST_REV shall be incremented at least by one if at
Unsigned16
least one static parameter in the corresponding
block has been modified
OctetString(32)
Unsigned16
Unsigned8
Unsigned8
Target mode
Record
Unsigned8
Actual mode
Unsigned8
Permitted mode
Unsigned8
Normal mode
Record
OctetString(2)
Current alarm
OctetString(2)
Unacknowledged alarm
OctetString(2)
Unreported alarm
OctetString(2)
Disabled alarm
Record
Primary value and status (Pressure)
Float
Primary value
Unsigned8
Primary status
Unsigned16
Primary value unit (Pressure engineering units)
Record
Secondary value and status (Process Temperature)
Float
Secondary value
Unsigned8
Secondary status
Unsigned16
Secondary value unit (Temperature units)
Record
Tertiary value and status (Ambient Temperature)
Float
Tertiary value
Unsigned8
Tertiary status
Unsigned16
Tertiary value init (Temperature units)
Record
Quaternary value and status (Pressure)
Float
Quaternary value
Unsigned8
Quaternary status